RGF-PKG™ Commercial Air Purification System
The RGF-PKG™ package unit uses RGF’s patented Photohydroionization® (PHI-CELL®) technology to reduce airborne and surface bacteria, viruses, odors, VOCs (chemical odors), and mold*. RGF-PKG™ package units are designed specifically for use where the supply duct is not accessible and large commercial applications. They utilize adjustable magnetic feet with vibration dampers to attach without fasteners to the HVAC blower unit or PKG Rack System, making installation fast and simple. RGF-PKG™ package units are available with 5″, 9″ and 14” PHI-CELLS®.
RGF’s new PKG-Rack™ systems are often used for commercial installations where several RGF-PKG™ package air purification units are required. Each PKG-Rack™ system provides convenient installation for up to eight (8) PKG-14 units. The PKG-Rack™ system offers customer the ability to quickly and efficiently add active air purification to the largest commercial air handlers and roof top HVAC systems.
Item # | HVAC Blower Size | Tonnage | Dimensions | Ship Weight | |
---|---|---|---|---|---|
PHI-PKG5-24V | 250* to 1,200 CFM | Up to 3.5 ton | 2.25"W x 10.5”L x 1.7"D | 1 lb. | |
PHI-PKG9-24V | 1,200 to 3,000 CFM | 3.5 to 7.5 ton | 2.25"W x 13.5”L x 1.75”D | 1 lb. | |
PHI-PKG14-24V | 3,000 to 8,000 CFM | 7.5 to 20 ton | 2.25"W x 18.5”L x 1.75”D | 2 lb. | |
CUV-PPS-KIT | N/A | N/A | N/A | N/A |
- Details
- Features & Benefits
- Applications
- Technical Specs
Why Use RGF’s Photohydroionization® Technology?
Photohydroionization® (PHI) is an active air treatment technology. Active air treatment is the process of reducing air and surface contaminants by recreating safe, natural levels of hydrogen peroxide (H2O2) in occupied areas.
RGF's patented PHI-CELL® technology combines a photocatalytic process and a multiwavelength UV source to create active air purification. The combination of UV light and a hydrated quad-metallic catalyst drives a reaction that produces low level, airborne H2O2. RGF's PHI-CELL® air treatment systems are operating safely in over four million installations globally.
• Kills bacteria, viruses and mold
• Reduces odors and VOCs (chemical odors)
• Easy, no-tool installation
• Small package products
• Vertical stack units
• Roof tops
• Gas package products
• Rental units where modification to the HVAC system is not allowed
• Anywhere ductwork is inaccessible
Item # | PHI-PKG5-24V | PHI-PKG9-24V | PHI-PKG14-24V |
---|---|---|---|
HVAC Blower Size | 250* to 1,200 CFM | 1,200 to 3,000 CFM | 3,000 to 8,000 CFM |
Tonnage | Up to 3.5 ton | 3.5 to 7.5 ton | 7.5 and 20 ton |
Dimensions | 2.25″W x 10.5”L x 1.75”D | 2.25″W x 13.5”L x 1.75”D | 2.25″W x 18.5”L x 1.75”D |
Ship Wt. | 1 lb. | 1 lb. | 2 lb. |
*Install unit in conjunction with an HVAC system utilizing a minimum air volume of 250 cfm. | |||
Replacement Cell Part # | PHIC-5PKG | PHIC-9PKG | PHIC-14PKG |
Description | Package PHI Cell 5” | Package PHI Cell 9” | Package PHI Cell 14” |
Technology | PHI-CELL® *RGF Proprietary Catalyst and UVC Lamp |
||
Recommended Cell Replacement | 18,000 – 25,000 hrs. | ||
Volts | 24 VAC | ||
Amps | 0.48 A | ||
Watts | 11 W | ||
Tonnage | Up to 20 tons | ||
CFM’s | 250 – 8,000 | ||
Installation | Air handler cabinet / magnetic mount | ||
Material | Aluminum | ||
Dimensions | 2.25” W x 10.5” L x 1.75” D | ||
Warranty | 2 years ballast / 2 years cell (U.S. only) | ||
Hydro-Peroxides | <.02 PPM |
Item # | CUV-PPS-KIT |
---|---|
Volts | 120/240 VAC |
Amps | 1.3/0.65 |
Watts | 150 |
Phase | 1 |
Hz | 50/60 |
SCCR | 5kA |
Certification | UL508 |
Certifications & Awards
UL 1598:2008 (3rd Edition)
CAN/CSA C22.2 No.250.0:2008
EN 60335-2-65/A1:2008